8.07 – Preventative Maintenance Schedule
The Facilities Maintenance Department work schedule: 40 hours per week; emergency on-call coverage 24 hours per day, 7 days per week.
The following list includes schedules for a variety of preventative maintenance. A dated schedule will be maintained by the maintenance department.
- Resident room heating and cooling unit filter cleaning as required—a dated schedule is in the corporate office.
- Main air conditioner condenser and cooling coil cleaned at beginning of cooling season and at mid-season.
- Furnaces checked and filters cleaned at beginning of season and as required.
- All refrigerator condensers cleaned every 6 months—a dated schedule is in the corporate office.
- Internal Operational check of fire alarm systems 3 times per month.
- Emergency lighting system and exit doors checked every month and serviced as needed.
- Inspect hot water heaters, drain and clean pilots every 6 months per instructions on unit.
- Parking lights checked quarterly for outages and repaired as needed.
- Clean smoke and heat detector filters at two-year intervals.
- Check smoke and heat detectors for red light outage at 30-day intervals.
- Fire extinguishers checked monthly for proper charge.
- Internal fire door check (check closure, for any damage, or other issues)
- Insect-control spray all units quarterly or as needed.
- Washers, dryers, and dishwashers serviced as required.
- Grease interceptors—bi-annual or as needed
- Sprinkler systems inspected quarterly by external vendor
- Internal inspection of attic (fill foam prohibited, check for penetrations; any repair needs to be done using fireproof rated materials)
- Internal inspection of sprinkler heads (if any corrosion, damage, missing escutcheon plates, paint spray over noted, must result in repair or replacement of sprinkler head by external vendor)
- Sprinkler sensitivity testing every 2 years by external inspector.
- Internal Generator checks to be completed weekly, with load test monthly
- Full Generator inspection and testing to be completed annually by external vendor.
- All outlets checked per standards with annual documentation on each outlet.
- Fire Door annual inspection per the fire door and annual egress inspection form.
- 5-year pipe inspection, hydrostatic testing to be completed by external inspector.
- 4-year damper inspection by external source.
- Empty locked ash tray containers.
- Complete water temperature tracking weekly.
- PSI systems semi-annually.
- Any preventative maintenance as assigned by Director or supervisor.
- Fire inspections by external fire support vendor quarterly, semi-annually, and annually.
- Back flow testing
- Fire Department inspection annually.
- Building code and occupancy inspection annually, or as needed.
Signed by:

Rebecca Sharp Porter
Chief Executive Director
Last Revised: 3/8/24